YASNAC PCNC I/O Signal Function Manual Chapter 10: Safety and Maintenance Functions

10.2 External Reset Input Signal and Resetting Output Signals

The external reset (ERS) is the input signal to reset the PCNC.

When the ERS input signal is “closed”, the PCNC stops the entire operation and closes the
resetting output signal for one second.

The output signals are “opened” with the exception as shown in Table 10.1.

Table 10.1 Output Signals which are “Closed”

IMPORTANT!

When the ERS input is “closed”, the CNC is in the label skip state. In this case, however, the tape
is not rewound; although, the memory is rewound.

Label skip:When the PCNC is in the label skip state, the information having been read until the

first end of the block code is read after power ON or reset, is ignored. There is no
parameter to cancel the label skip state.

External Reset Input Signal

ERS

#30041

Resetting Output Signal

RSTS

#35001

Output Signal

Name

Output when ERS Input is “Closed”

AUT, MAN
ZPX to ZP5

2ZPX to 2ZP5
3ZPX to 3ZP5
4ZPX to 4ZP5
5ZPX to 5ZP5

4NGC, 5NGC

The previous state is maintained.

RSTS

“Closed” while ERS input is “closed”,
and “closed” for one second after the
ERS input is changed from “closed” to
“opened”.

ALMS

Remains “opened” unless

the cause of alarm remains

SDO0 to SDO23

The previous state is maintained.

UO0 to UO31

The previous state is maintained.