Setup and Installation 3-3

Option Board Setup


The DeviceNet Option Board requires setup prior to operation. DIP switches must be set prior to the application
of input AC power to the Drive. The states of these DIP switches are read only on power-up.

Option Board DIP Switch Settings


The DIP switches are used to setup DeviceNet network characteristics. The DIP switch functions are defined in
the following table:

DIP Switch Number

Function

1

Baud Rate, Bit 1

2

Baud Rate, Bit 0

3

Node Number, MSB

4 Node

Number

5 Node

Number

6 Node

Number

7 Node

Number

8

Node Number, LSB

9 Not

Used

10

Master Idle Operation


DIP switches 1 and 2 are used to select the baud rate of the DeviceNet network. The baud rate setting of the
Option Board must match the baud rate setting of the rest of the devices on the DeviceNet network. The
available baud rates are defined in the following table. The cable distance between any two points in the cable
system must not exceed the Maximum Cable Distance allowed for the baud rate selected. See Chapter 4 for
information on calculating the Maximum Cable Distance.

DeviceNet

Baud Rate

DIP Switch Position

(KBaud)

Switch 1

Switch 2

125 Off

Off

250 Off

On

On Off

500

On On