Setup and Installation 3-5

Some master devices can be placed in idle mode. During idle mode, some masters do not send or receive
polled messages. DIP switch 10, allows the drive to continue to operate as normal or generate an “EF0” fault to
indicate that no polled messages are being received from the master.

Master Idle

DIP Switch Position

Operation

Switch 10

“EF0” disabled

Off

“EF0” enabled

On


With DIP switch 10 in the “Off” position, the “EF0” fault is disabled. When the master is placed in idle mode, the
drive will continue to operate as normal based on the last polled message that was received from the master.

With DIP switch 10 in the “On” position, the “EF0” fault is enabled. When the master is placed in idle mode, the
drive will generate an “EF0” fault. The drive returns to normal operation after the master is no longer in idle
mode, the run command is removed, and the RESET command is issued via DeviceNet, control terminals, or the
Drive Digital Operator.