Configuration of Drive DeviceNet Parameters 6-2

Polled Configuration


The Drive DeviceNet Polled connection must be configured before receiving commands from a Master device.
The two parameters that must be configured are:

• Polled Consuming Assembly
• Polled Producing Assembly



The PCA and PPA parameters can be accessed in various ways. If your configuration tool uses the EDS files for
configuration, the PCA and PPA parameters can be accessed from the “DN: Polled Config” parameter group. If
your configuration tool uses an alternate form of configuration, a DeviceNet path may be required. The following
table shows both the EDS locations and the DeviceNet path for the PCA and PPA. Please refer to Appendix A for
further details on DeviceNet path information.

Polled

Parameter

EDS

Param #

DeviceNet

Path

Polled Consuming Assembly

28

Class5 / Instance2 / Attribute101

Polled Producing Assembly

29

Class5 / Instance2 / Attribute100


The PCA and PPA values may be changed at any time, whether the Drive is running or stopped. However, it is
not recommended that these values be changed while the Drive is running.

CAUTION

The Drive should be stopped before changing PCA and PPA values.

Cycle the power to the Drive after changing the PCA and PPA values.