Amprobe, Multitest2000 – Amprobe Multitest-2000 Continuity-Tester User Manual

Page 135

Advertising
background image

AMPROBE

MULTITEST2000

RCD and LOOP function are active only for 50Hz

± 0,5Hz frequency

VOLTAGE MEASUREMENT (PHASE ROTATION)

Range [V]

Resolution [V]

Accuracy

0

÷ 460V

1

±(3%Reading + 2digit)

EARTH: GROUND RESISTANCE MEASUREMENT WITH EARTH RODS

Range RE [

]

Resolution [

]

Accuracy

0.01 – 19.99
20.0 – 199.9

200 - 1999

0.01

0.1

1

±(5% Reading + 3 digit)

Test Current

<10mA – 77.5Hz

Open circuit Test Voltage

<20V RMS

RESISTIVITY MEASUREMENT

Range

ρ

Resolution

Accuracy

0.60

÷19.99 Ωm

20.0

÷ 199.9Ωm

200

÷ 1999Ωm

2.00

÷ 99.99kΩm

100.0

÷ 125.6kΩm(*)

0.01

Ωm

0.1

Ωm

1

Ωm

0.01 k

Ωm

0.1 k

Ωm

±(5% Reading + 3 digit)

(*) setting distance = 10m
Test Current

<10mA – 77.5Hz

Open circuit Test Voltage

<20V RMS


Advertising