Amprobe, Warning – Amprobe Multitest-2000 Continuity-Tester User Manual

Page 28

Advertising
background image

AMPROBE

MULTITEST2000

6.1.2. Measurement Procedure

1. Select the desired mode using the F1 key.
2. Connect the black and blue test leads to B1 and B4 input terminals respectively

B2

B3

B4

B1

Connection of the test leads during LOW

test.

3. If the cables supplied with the instrument are not long enough for the measurement

you can extend the blue cable.

4. Short-circuit the test leads making sure that the conductive parts of the alligator clips

make a good contact to each other. Press the START key. If the display doesn't
show 0.00

repeat the test leads calibration (see paragraph 6.1.1).

5. Connect the instrument terminals to the ends of the conductor under test (see

previous picture).

6. If the mode "RT+" or "RT-" was selected use the F3, F4 keys to set the

duration of the test.

7. Press the START key. The instrument will execute the measurement. In RT+/RT-

(Timer mode) you can press START key again if you want to stop the test before the
duration set is expired.

ν

WARNING:

Never disconnect the test leads when the message
"Measuring" is displayed.

START

STOP