16.3. Measurement Of Floor Insulation Resistance In Medical Rooms Cei 64-4

PURPOSE OF THE TEST

Check that the floor is made of material whose insulation resistance complies with the
requirements of the standards CEI 64-4 (3.05.03).

INSTALLATION PARTS TO BE CHECKED

The test shall be effected between:

a)

Two electrodes whose distance to each other shall be one meter.

b)

One electrode on the floor and the equalising potential node.