Amprobe – Amprobe Multitest-2000 Continuity-Tester User Manual
Page 38

AMPROBE
MULTITEST2000
6.2.2. Results of "MAN" mode
M
Ω 05.06.01
Insulation Resistance
Voltage during the Test
Duration of the Test
Test mode
1.07
M
Ω
514V 15s
MAN 500V
Test voltage set
FUNC
VNOM
At the end of the test if
the insulation
resistance is lower
than R
MAX
(see Table2)
and the instrument
generates the
Nominal test Voltage,
the instrument emits a
double beep,
indicating the positive
outcome of the test
and displays a screen
similar to the screen to
the right.
In order to evaluate the test you must compare the result with the limits indicated in the
Guidelines (see Table1).
The displayed result can be stored pressing the SAVE key twice (according to
paragraph 9.1).
M
Ω 05.06.01
Maximum resistance value
which can be measured
(999
Ω is displayed if a
rated voltage of 500V was
selected, see Table2).
If the Insulation
resistance is higher
than R
MAX
(see Table2),
the instrument emits a
double beep at the end
> 999
M
Ω