MULTITEST2000

6.2. M

: INSULATION RESISTANCE MEASUREMENT WITH 50V, 100V, 250V,

500V, 1000V TEST VOLTAGE

The measurements comply with IEC 61557-2 and VDE 0413 part 1.

ν

ATTENTION:

Before performing an insulation test make sure that the circuit
under test is not energised and all the loads are disconnected.

Turn the rotary knob to the M

Ω position.


The F1 key allows the operator to select one of the following measuring
modes:

MAN mode (Manual mode) Recommended test.
TMR mode (Timer mode: test duration depends on the selected interval

from 10 to 999 seconds). This test can be executed when the test
required a defined duration.


6.2.1. Measurement

Procedure

1. Select the desired mode using the F1 key.
2. Connect the test leads to the instrument input terminals B1 and B4 respectively,