Amprobe – Amprobe Multitest-2000 Continuity-Tester User Manual

Page 36

Advertising
background image

AMPROBE

MULTITEST2000

Standard

Brief description

Test voltage

Maximum limit value

CEI 64-8/6

Systems SELV or PELV

Systems up to 500V (Civil installations)

Systems over 500V

250VDC
500VDC

1000VDC

> 0.250M

> 0.500M

> 1.0M

CEI 64-8/4

Floor and wall insulation in civil installations

Floor and wall insulation in systems over 500V

500VDC

1000VDC

> 50k

Ω (se V<500V)

> 100k

Ω (se V>500V)

EN60439

Electrical panel boards 230/400V

500VDC

> 230k

EN60204

Electrical equipment of machines

500VDC

> 1M

CEI 64-4

Floor insulation in medical rooms

500VDC

<1M

Ω (if the floor is at least 1 year old)

<100M

Ω (if the floor is at least 1year old)

Table1:

Table reporting the test voltage and the corresponding limit values for
few Guidelines.

Rated voltage selected

for the test

R

MAX

= Maximum resistance

value

50VDC

99.9M

100VDC

199.9M

250VDC

499M

500VDC

999M

1000VDC

1999M

Table2:

Table of maximum resistance values which can be measured under M

mode depending on the rated voltage selected.



6. If the "TMR" mode was selected use the F3, F4 keys to set the duration time of

the test: