M
Ω 05.06.01
Insulation Resistance
ν 1.17
M
Ω
107V 15s
MAN 500V
ATTENTION: the test of
resistance R
ISO
was taken at a
voltage value lower than the
set rated voltage. Low
insulation case. This case
occurs under low insulation
conditions or in the presence of
capacitance on the installation.
FUNC
VNOM
If the instrument can't
generate the Nominal
Test Voltage it will
emit a long beep and
displays a screen
similar to the screen
to the right.
Test Duration
The displayed result can be stored by pressing the SAVE key twice (refer to
paragraph 9.1).
6.3.
: PHASE
SEQUENCE
INDICATOR
Turn the rotary knob to the
position.
6.3.1. Measurement procedure and results of "
" mode
1. Connect the Black, Red and Green connectors of the split cables to their
corresponding input terminals of the instrument B1, B2, B3.