MVI56E-MCMR ♦ ControlLogix Platform

Verify Communication

Modbus Communication Module with Reduced Data Block

User Manual

ProSoft Technology, Inc.

Page 111 of 225

May 13, 2014

Based on these values shown above, a good place for the M

ODBUS

P

ORT X

C

OMMAND

E

RROR

P

OINTER

is address 1500, as shown.

With the C

OMMAND

E

RROR

P

OINTER

set to address 1500, this will place your

Command Error Data at addresses starting at 1500 of the module memory, and
because of the before mentioned configuration of the B

ACKPLANE

C

ONFIGURATION

R

EAD

R

EGISTER

S

TART

and R

EAD

R

EGISTER

C

OUNT

parameters,

the command error data will be placed into the tags beginning at
MCMR.DATA.R

EAD

D

ATA

[500].

Each command configured in the M

ODBUS

P

ORT X

C

OMMANDS

will occupy one

register within the R

EAD

D

ATA

array. For a command list consisting of 100

commands, the following table is true.

Error Code for Command

ReadData Location

1

MCMR.DATA.ReadData[500]

2

MCMR.DATA.ReadData[501]

3

MCMR.DATA.ReadData[502]

4

MCMR.DATA.ReadData[503]

5

MCMR.DATA.ReadData[504]

90

MCMR.DATA.ReadData[598]

99

MCMR.DATA.ReadData[599]