MVI56E-MCMR ♦ ControlLogix Platform

Diagnostics and Troubleshooting

Modbus Communication Module with Reduced Data Block

User Manual

ProSoft Technology, Inc.

Page 139 of 225

May 13, 2014

The port configuration error words have the following definitions:

Bit

Description

Value

0

Type code is not valid. Enter a value from 0 (Master) to 1
(Slave).

0x0001

1

The float flag parameter is not valid.

0x0002

2

The float start parameter is not valid.

0x0004

3

The float offset parameter is not valid.

0x0008

4

Protocol parameter is not valid.

0x0010

5

Baud rate parameter is not valid.

0x0020

6

Parity parameter is not valid.

0x0040

7

Data bits parameter is not valid.

0x0080

8

Stop bits parameter is not valid.

0x0100

9

Slave ID is not valid.

0x0200

10

Input bit or word, output word and/or holding register
offset(s) are not valid.

0x0400

11

Command count parameter is not valid.

0x0800

12

Spare

0x1000

13

Spare

0x2000

14

Spare

0x4000

15

Spare

0x8000

Correct any invalid data in the configuration for proper module operation. When
the configuration contains a valid parameter set, all the bits in the configuration
words will be clear. This does not indicate that the configuration is valid for the
user application. Make sure each parameter is set correctly for the specific
application.

Note: If the APP, BP ACT and OK LEDs blink at a rate of every one-second, this indicates a
serious problem with the module. Call ProSoft Technology Support to arrange for repairs.