MVI56E-MCMR ♦ ControlLogix Platform

Reference

Modbus Communication Module with Reduced Data Block

User Manual

ProSoft Technology, Inc.

Page 157 of 225

May 13, 2014

Block Request from Processor to Module

Word Offset

Definitions

0

Enable (must be set to 1)

1

Internal DB Address (0-4999)

2

Poll Interval (set to 0)

3

Count (1-125, or maximum supported by the target Slave device)

4

Swap (0, 1, 2, or 3)

5

Device (Modbus Slave Device Address Number of target Slave)

6

Function (Modbus Function Code: 1, 2, 3, 4, 5, 6, 15, or 16)

7

Device Address (0-9999, address offset in target Slave database)

8

Reserved (set to 0)

9

Reserved (set to 0)

Refer to Master Command Configuration (page 60) for a detailed definition of the
fields contained in this block. They are the same as those used in constructing
the commands in ProSoft Configuration Builder (PCB) in the M

ODBUS

P

ORT

1

C

OMMANDS

or M

ODBUS

P

ORT

2

C

OMMANDS

lists.

The Send Event Command message uses the following parameters in the MSG