Reference

Modbus Communication Module with Reduced Data Block

User Manual

ProSoft Technology, Inc.

Page 205 of 225

May 13, 2014

4 Click OK

to save your module settings. This action opens the M

ODULE

P

ROPERTIES

dialog box.

5 In the C

ONNECTION

tab, the Requested Packet Interval (RPI) value represents

the time interval at which the module will attempt backplane communication
with the processor. This value should not be set to less than 1 millisecond.
Values between 1 and 10 milliseconds should work with most applications. If
the module is installed in a Remote chassis and accessed via ControlNet, the
RPI must not be set to a value lower than the ControlNet Network Update
Time (NUT). Doing so will cause scheduling errors in RSNetworx for
ControlNet.

6 Click OK

to save your settings. Notice that the module now appears in the

C

ONTROLLER

O

RGANIZATION

window.