MVI56E-MCMR ♦ ControlLogix Platform

Reference

Modbus Communication Module with Reduced Data Block

User Manual

ProSoft Technology, Inc.

Page 189 of 225

May 13, 2014

Response
The normal response will be an echo of the Slave address, function code,
starting address, and quantity of coils forced.

Adr

Func

Hi Addr

Lo Addr

Quantity

Error Check Field

11

0F

00

13

00

0A

CRC

The writing of coils via Modbus function 15 will be accomplished regardless of
whether the addressed coils are disabled or not.

Coils that are unprogrammed in the controller logic program are not automatically
cleared upon power up. Thus, if such a coil is set ON by function code 15 and
(even months later) an output is connected to that coil, the output will be hot.

6.6.10 Preset Multiple Registers (Function Code 16)

Query
Holding registers existing within the controller can have their contents changed
by this message (a maximum of 60 registers). However, because the controller is
actively scanning, it also can alter the content of any holding register at any time.
The values are provided in binary up to the maximum capacity of the controller
(16-bit for the 184/384 and 584); unused high order bits must be set to zero.

Note: Function codes 5, 6, 15, and 16 are the only messages that will be recognized as valid for
broadcast.

Adr

Func

Hi
Add

Lo Add

Quantity

Byte
Cnt

Hi
Data

Lo
Data

Hi
Data

Lo Data Error Check

Field

11

10

00

87

00

02 04

00

0A

01

02

CRC

Response
The normal response to a function 16 query is to echo the address, function
code, starting address and number of registers to be loaded.

Adr

Func

Hi Addr

Lo Addr

Quantity

Error Check Field

11

10

00

87

00

02

56