MVI56E-MCMR ♦ ControlLogix Platform

Reference

Modbus Communication Module with Reduced Data Block

User Manual

ProSoft Technology, Inc.

Page 147 of 225

May 13, 2014

6.2.3 General Specifications - Modbus Master/Slave

Communication
parameters

Baud Rate: 110 to 115K baud
Stop Bits: 1 or 2
Data Size: 7 or 8 bits
Parity: None, Even, Odd
RTS Timing delays: 0 to 65535 milliseconds

Modbus Modes

RTU mode (binary) with CRC-16
ASCII mode with LRC error checking

Floating Point Data

Floating point data movement supported, including configurable
support for Enron, Daniel

®

, and other implementations

Modbus Function Codes
Supported

1: Read Coil Status
2: Read Input Status
3: Read Holding Registers
4: Read Input Registers
5: Force (Write) Single Coil
6: Preset (Write) Single
Holding Register
8: Diagnostics (Slave Only,
Responds to
Subfunction 00)

15: Force( Write) Multiple Coils
16: Preset (Write) Multiple
Holding Registers
17: Report Slave ID (Slave Only)
22: Mask Write Holding
Register (Slave Only)
23: Read/Write Holding
Registers (Slave Only)

6.2.4 Functional Specifications

Modbus Master
A port configured as a virtual Modbus Master actively issues Modbus commands
to other nodes on the Modbus network, supporting up to 100 commands on each
port. The Master ports have an optimized polling characteristic that polls slaves
with communication problems less frequently.

Command List

Up to 100 command per Master port, each fully configurable for
function, slave address, register to/from addressing and word/bit
count.

Polling of command list

Configurable polling of command list, including continuous and on
change of data, and dynamically user or automatic enabled.

Status Data

Error codes available on an individual command basis. In addition,
a slave status list is maintained per active Modbus Master port.

Modbus Slave
A port configured as a Modbus slave permits a remote Master to interact with all
data contained in the module. This data can be derived from other Modbus slave
devices on the network, through a Master port, or from the ControlLogix
processor.

Node address

1 to 247 (software selectable)

Status Data

Error codes, counters and port status available per configured slave
port