ProSoft Technology MVI56E-MCMR User Manual
Page 93
Advertising

MVI56E-MCMR ♦ ControlLogix Platform
Configuring the MVI56E-MCMR Module
Modbus Communication Module with Reduced Data Block
User Manual
ProSoft Technology, Inc.
Page 93 of 225
May 13, 2014
5
The module’s default IP address is 192.168.0.250. Choose an unused IP
within your subnet, and then click OK.
Important: The temporary IP address is only valid until the next time the module is initialized. For
information on how to set the module’s permanent IP address, see Ethernet Configuration (page
90).
6 Close the ProSoft Discovery Service window. Enter the temporary IP in the
Ethernet address field of the Connection Setup dialog box, then click the
T
EST
C
ONNECTION
button to verify that the module is accessible with the
current settings.