ProSoft Technology MVI56E-MCMR User Manual

Page 174

Advertising
background image

Reference

MVI56E-MCMR ♦ ControlLogix Platform

User Manual

Modbus Communication Module with Reduced Data Block

Page 174 of 225

ProSoft Technology, Inc.

May 13, 2014

RS-232: Null Modem Connection (No Hardware Handshaking)

This type of connection can be used to connect the module to a computer or field
device communication port.

Note: For most null modem connections where hardware handshaking is not required, the Use
CTS Line
parameter should be set to N

and no jumper will be required between Pins 7 (RTS) and 8

(CTS) on the connector. If the port is configured with the Use CTS Line set to Y, then a jumper is

required between the RTS and the CTS lines on the port connection.