MVI56E-MCMR ♦ ControlLogix Platform

Configuring the MVI56E-MCMR Module

Modbus Communication Module with Reduced Data Block

User Manual

ProSoft Technology, Inc.

Page 67 of 225

May 13, 2014

Parameter

Description

Enable = 1

The module will send the command every time it goes through the
command list.

Internal Address = 1010

Places the data read from the slave device into the module at
address 1010. Internal Address 1010 of the module memory will be
copied into the tag MCMR.DATA.R

EAD

D

ATA

[10].

Reg Count = 10

Reads 10 consecutive registers from the slave device.

Node Address = 1

Issues the Modbus command to Modbus Slave Device Address 1.

Modbus Function =4

Issues Modbus Function Code 4 to Read Input Registers.

MB Address in Device =20

Function Code 4 MB Address in Device of 20 will read address 30021
Along with a count of 10, this command reads 30021 to 30030.