MVI56E-MCMR ♦ ControlLogix Platform

Diagnostics and Troubleshooting

Modbus Communication Module with Reduced Data Block

User Manual

ProSoft Technology, Inc.

Page 125 of 225

May 13, 2014

Operation Messages
After the initialization step, the following message pattern will be repeated.

<Backplane Status> <IP Address> <Backplane Status> <Port Status>

Code

Message

<Backplane Status>

OK: Module is communicating with processor
ERR: Module is unable to communicate with processor. For
this scenario, the <Port Status> message above is replaced
with "Processor faulted or is in program mode".

<IP Address>

Module IP address

<Port Status>

OK: Port is communicating without error
Master/Slave Communication Errors: port is having
communication errors. Refer to PCB diagnostics (page 122,
page 130) for further information about the error.

5.1.2 Non-Scrolling LED Status Indicators

The non-

scrolling LEDs indicate the module’s operating status as follows:

LED Label

Color

Status

Indication

APP

Red or
Green

OFF

The module is not receiving adequate power or is not securely
plugged into the rack. May also be OFF during configuration
download.

GREEN

The MVI56E-MCMR is working normally.

RED

The most common cause is that the module has detected a
communication error during operation of an application port.
The following conditions may also cause a RED LED:

The firmware is initializing during startup

The firmware detects an on-board hardware problem
during startup

Failure of application port hardware during startup

The module is shutting down

The module is rebooting due to a ColdBoot or WarmBoot
request from the ladder logic or Debug Menu

OK

Red or
Green

OFF

The module is not receiving adequate power or is not securely
plugged into the rack.

GREEN

The module is operating normally.

RED

The module has detected an internal error or is being
initialized. If the LED remains RED for over 10 seconds, the
module is not working. Remove it from the rack and re-insert it
to restart its internal program.

ERR

Red

OFF

The battery voltage is OK and functioning.

ON

The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for 24
hours. If ERR LED still does not go off, contact ProSoft
Technology, as the battery is not a user-serviceable item.