MCMREventCmd
When the command bit (MCMR.CONTROL.E

VENT

T

RIGGER

P

X

) is set in the

example ladder logic, the module will build a block 9901 with the command
contained in the first command of the MCMR.CONTROL.E

VENT

C

MD

P

X

[ ]

array.

The module will receive this block and build and send the command to the
specified control device using a MSG block.

The following table describes the data for the command element in the
MCMRE

VENT

C

MD

array.

Name

Data Type

Description

Enable

INT

0=Disable, 1=Continuous, 2=Event Command

IntAddress

INT

Module’s internal address associated with the
command

PollInt

INT

Minimum number of seconds between issuance
of command (0 to 65535 Sec)

Count

INT

Number of registers associated with the
command

Swap

INT

Swap code used with command

Device

INT

Device index in Device Table to associate with
the command

Func

INT

Function code for the command

DevAddress

INT

Address in device associated with the command

MCMRCmdControl
When the command bit (MCMR.CONTROL.C

MD

C

ONTROL

P

X

.C

MD

T

RIGGER

) is set

in the example ladder logic, the module will build a block 9901 with the number of
commands set through:
MCMR.CONTROL.C

MD

C

ONTROL

P

X

.C

MD

C

ONTROL

D

ATA

[0].

The command indexes will be set through the controller tags starting from
MCMR.CONTROL.C

MD

C

ONTROL

P

X

.C

MD

C

ONTROL

D

ATA

[1]

to

MCMR.CONTROL.C

MD

C

ONTROL

P

X

.C

MD

C

ONTROL

D

ATA

[20]

For example, in order to enable commands 0, 2 and 5 the following values would
be set:

MCMR.CONTROL.C

MD

C

ONTROL

P

X

.C

MD

C

ONTROL

D

ATA

[0]

=

3

MCMR.CONTROL.C

MD

C

ONTROL

P

X

.C

MD

C

ONTROL

D

ATA

[1]

=

0

MCMR.CONTROL.C

MD

C

ONTROL

P

X

.C

MD

C

ONTROL

D

ATA

[2]

=

2

MCMR.CONTROL.C

MD

C

ONTROL

P

X

.C

MD

C

ONTROL

D

ATA

[3]

=

5

The module will receive this block and build and send the command to the
specified control device using a MSG block.

The following table describes the data for the command element in
MCMRC

MD

C

ONTROL

.

Name

Data Type

Description

CmdTrigger

BOOL

Command Trigger

CmdControlData

INT[21]

Command Control Data

CmdControlResp

INT[5]

Command Control Response

CmdErrTrigger

BOOL

Command Error Trigger

CmdErrData

INT[102]

Command Error Data

Advertising