MVI56E-MCMR ♦ ControlLogix Platform

Configuring the MVI56E-MCMR Module

Modbus Communication Module with Reduced Data Block

User Manual

ProSoft Technology, Inc.

Page 83 of 225

May 13, 2014

Modbus Memory Map

Based on the configuration described above, below is the default Modbus
address for the module. Each register within the module can be accessed as a
0x bit address, 1x bit address, 3x register address, or 4x register address.

MVI Address

0x

1x

3x

4x

Tag Address

0

0001 to 0016

10001 to 10016

30001

40001

WriteData[0]

1

0017 to 0032

10017 to 10032

30002

40002

WriteData[1]

2

0033 to 0048

10033 to 10048

30003

40003

WriteData[2]

3

0049 to 0064

10049 to 10064

30004

40004

WriteData[3]

4

0065 to 0080

10065 to 10080

30005

40005

WriteData[4]

5

0081 to 0096

10081 to 10096

30006

40006

WriteData[5]

6

0097 to 0112

10097 to 10112

30007

40007

WriteData[6]

7

0113 to 0128

10113 to 10128

30008

40008

WriteData[7]

8

0129 to 0144

10129 to 10144

30009

40009

WriteData[8]

9

0145 to 0160

10145 to 10160

30010

40010

WriteData[9]

10

0161 to 0176

10161 to 10176

30011

40011

WriteData[10]

50

0801 to 0816

10801 to 10816

30051

40051

WriteData[50]

100

1601 to 1616

11601 to 11616

30101

40101

WriteData[100]

200

3201 to 3216

13201 to 13216

30201

40201

WriteData[200]

500

8001 to 8016

18001 to 18016

30501

40501

WriteData[500]

598

9569 to 9584

19569 to 19584

30599

40599

WriteData[598]

599

9585 to 9600

19585 to 19600

30600

40600

WriteData[599]

600 to 999

N/A

N/A

N/A

N/A

Reserved

1000

31001*

41001

ReadData[0]

1001

31002*

41002

ReadData[1]

1002

31003*

41003

ReadData[2]

1003

31004*

41004

ReadData[3]

1004

31005*

41005

ReadData[4]

1005

31006*

41006

ReadData[5]

1006

31007*

41007

ReadData[6]

1007

31008*

41008

ReadData[7]

1008

31009*

41009

ReadData[8]

1009

31010*

41010

ReadData[9]

1010

31011*

41011

ReadData[10]

1050

31051*

41051

ReadData[50]

1100

31101*

41101

ReadData[100]

1200

31201*

41201

ReadData[200]

1500

31501*

41501

ReadData[500]

1598

31599*

41599

ReadData[598]

1599

31600*

41600

ReadData[599]

The above addressing chart will work with many Modbus applications. Values
listed in the ReadData array for 31001 to 31600 are shown with an * beside
them.