ProSoft Technology MVI56E-MCMR User Manual

Page 76

Advertising
background image

Configuring the MVI56E-MCMR Module

MVI56E-MCMR ♦ ControlLogix Platform

User Manual

Modbus Communication Module with Reduced Data Block

Page 76 of 225

ProSoft Technology, Inc.

May 13, 2014

Read Multiple Floating-Point Registers

The following table is an example to read Multiple Floating-Point values and
device addresses. The table shows 7 consecutive floating-point values (14
Modbus addresses).

Value

Description

Type

40261

KW

Demand (power)

Float. upper 16 bits

40263

VAR

Reactive Power

Float. upper 16 bits

40265

VA

Apparent Power

Float. upper 16 bits

40267

Power Factor

Float. upper 16 bits

40269

VOLTS

Voltage, line to line

Float. upper 16 bits

40271

VOLTS

Voltage, line to neutral

Float. upper 16 bits

40273

AMPS

Current

Float. upper 16 bits

Configure the command to read these 7 floats as follows.

Configure an array of 7 floats within the ControlLogix processor as shown in the
following illustration.

The following COP

statement will copy the data from MCMR.DATA.R

EAD

D

ATA

[0]

TO

[13]

into the array MCM_F

LOAT

_D

ATA

[0]

TO

[6].

The "Length" parameter is set to the number of Floating-Point values that must
be copied from the MCMR.DATA.R

EAD

D

ATA

array.