Diagnostics and Troubleshooting

MVI56E-MCMR ♦ ControlLogix Platform

User Manual

Modbus Communication Module with Reduced Data Block

Page 140 of 225

ProSoft Technology, Inc.

May 13, 2014

5.4.1 Clearing a Fault Condition

Typically, if the OK LED on the front of the module turns RED for more than ten
seconds, a hardware problem has been detected in the module or the program
has exited.

To clear the condition, follow these steps:

1 Turn off power to the rack.
2 Remove the card from the rack.
3 Verify that all jumpers are set correctly.
4 If the module requires a Compact Flash card, verify that the card is installed

correctly.

5 Re-insert the card in the rack and turn the power back on.
6 Verify correct configuration data is being transferred to the module from the

ControlLogix controller.

If the module's OK LED does not turn GREEN, verify that the module is inserted
completely into the rack. If this does not cure the problem, contact ProSoft
Technology Technical Support.