ProSoft Technology PTQ-AFC User Manual

Page 112

Advertising
background image

Quick Start

PTQ-AFC ♦ Modicon Quantum Platform

User Manual

Liquid and Gas Flow Computer for Hydrocarbon Products

Page 112 of 259

ProSoft Technology, Inc.

June 23, 2011

bit 12 API calculation error, density correctio -

bit 13 API calculation error, Ctl -

bit 14 API calculation error, vapor pressure -

bit 15 API calculation error, Cpl -

Status

Bits

bit 11 Meter was enabled -

bit 12 Backplane communication fault -

bit 13 Measurement configuration changed yes

bit 14 Power up yes

bit 15 Cold start -

AFC-56(16) Daily Archive Date: 16-09-2002 16:26:51

Site Name: MVI Flow Station

Project: AFC

___________________________________________________________________________

Meter 1:

Tag M01

Archive 3

Closing timestamp of archive 2002-04-26.06:16:34

Opening timestamp of archive 2002-04-26.06:14:08

Status bitmap (details below) 20h

Alarms bitmap (details below) 0000h

Flowing period 146

Event counter 50

Net accumulator (x f3) 1633

Net accumulator residue (x f3) 6,271362E-02

Net flow rate (x f3/h) 40248,02

Temperature (°F) 14,99999

Pressure (psig) 1000,002

Differential pressure (hw) 22,00003

Relative density (60°F/60°F) 0,7404

Reference compressibility 0,9989

Flowing compressibility 0,9051

Fpv 1,0505

Velocity of approach factor Ev 1,0328

Expansion factor Y 0,9997

Discharge coefficient 0,6043

Alarm

Bits

bit 0 Temperature input out of range -

bit 1 Pressure input out of range -

bit 2 Diff. pressure input out of range -

bit 3 Flowing density input out of range -

bit 4 Water content input out of range -

bit 5 Diff. pressure low -

bit 8 Orifice characterization error -

bit 9 Analysis total zero -

bit 10 Analysis total not normalized -

bit 11 AGA8 calculation error -

bit 12 API calculation error, density correctio -

bit 13 API calculation error, Ctl -

Advertising
This manual is related to the following products: