ProSoft Technology PTQ-AFC User Manual

Page 79

Advertising
background image

PTQ-AFC ♦ Modicon Quantum Platform

Quick Start

Liquid and Gas Flow Computer for Hydrocarbon Products

User Manual

ProSoft Technology, Inc.

Page 79 of 259

June 23, 2011

6.8.2 Primary

Slave

The Primary Slave contains the main AFC database that consists of 131,072
Modbus registers. The Site and Meter configuration, as well as all live process
data and ongoing calculations are kept in the Primary Slave address space. This
address space is divided equally between the Input Register Bank (65,536
registers) and the Holding Register Bank (65,536).
The register addressing is shown in the Modbus Dictionary dialog box in AFC
Manager.

Modbus Address References
In these documents (the AFC Manager User’s Guide and the User’s Guide for
your platform) you will occasionally see Modbus address references like
Ph00018

or Mh00162. The first two characters of such references indicate how

to convert the following number into an absolute Modbus address in the module.
This table shows the possible values for the first identification character:

Address Translation ID

Description

P

Absolute Modbus address, Primary Slave

M

Meter-relative Modbus address, Primary Slave

V

Absolute Modbus address, Virtual Slave

This table shows the possible values for the second identification character:

Register Bank ID

Description

h

Holding register

i

Input register

Modbus Address Examples

Ph02000

= holding register located at address 2000 in the primary slave

Pi02000

= input register located at address 2000 in the primary slave

Mh00100

= Meter-relative holding register located at offset 100 in the block of the

primary slave that contains the data for the meter

Advertising
This manual is related to the following products: