PTQ-AFC ♦ Modicon Quantum Platform

Meter Proving

Liquid and Gas Flow Computer for Hydrocarbon Products

User Manual

ProSoft Technology, Inc.

Page 161 of 259

June 23, 2011

38

Master meter in calibration

The master meter has at least one process input in
calibration mode. Ensure that all process inputs are
live

before attempting to use the master meter for

proving.

39

Master meter not enabled

The master meter is not enabled.

51

Invalid prover parameter

For a traditional (non-master-meter) prover, the base
prover volume (register 65036) must be greater than
zero, and, if the prover is single-walled, the inside
diameter, wall thickness, and modulus of elasticity
(registers 65038, 65040, and 65042) must all be
greater than zero.

52

Invalid prover controls

Some undefined bits in the at-enable controls
(register 65306 bits 0 through 7) have been set.