Quick Start

PTQ-AFC ♦ Modicon Quantum Platform

User Manual

Liquid and Gas Flow Computer for Hydrocarbon Products

Page 88 of 259

ProSoft Technology, Inc.

June 23, 2011

Example
The following table shows how the data types are implemented if a write function
is selected and the item count is configured with a value of 10 (decimal):

Data Type

Register
Type

Modbus
Function

Number of
Coils

Number of
Bytes

Number of
Registers

Number of words
(16-bits)
transferred

Bit

Coil 15 10

2

-

1

Word

Holding 16

-

20

10

10

Long

Holding 16

-

40

20

20

Long Remote

Holding 16

-

40

10

20

Note: The number of coils, bytes, and registers are part of the Modbus request (functions 15 and
16) according to the Modbus specification.

The following table shows how the data types are implemented if a read function
is selected and the item count is configured with a value of 10 (decimal):

Data Type

Register Type

Modbus Function

Number of Registers

Bit

Coil 1

10

Bit

Input 2

10

Word

Holding 3

10

Word

Input 4

10

Long

Holding 3

20

Long

Input 4

20

Long Remote

Holding 3

10

Long Remote

Input 4

10

Note: The number of registers is part of the Modbus request according to the Modbus
specification.

Refer to the ladder logic section for your module for more information about the
Modbus Master block.