ProSoft Technology PTQ-AFC User Manual

Page 92

Advertising
background image

Quick Start

PTQ-AFC ♦ Modicon Quantum Platform

User Manual

Liquid and Gas Flow Computer for Hydrocarbon Products

Page 92 of 259

ProSoft Technology, Inc.

June 23, 2011

Each Resettable Accumulator can be configured to represent a different quantity
as follows:

Accumulator

Modbus address for accumulator
select (Meter-relative)

Default Value

Resettable accumulator 1

136

Net (code 3)

Resettable accumulator 2

137

Gross (code 4)

Resettable accumulator 3

138

Gross Standard (code 5)

Resettable accumulator 4

139

Mass (code 1)

Valid Configuration Codes
The valid codes are:

Code

Quantity

0

None

1

Mass

2

Energy (Gas Only)

3

Net

4

Gross

5

Gross Standard (Liquid Only)

6

Water (Liquid Applications Only).

For example, moving a value of 4 to holding register 8136 will configure Meter 1’s
resettable accumulator 1 as "Gross Volume". Moving "0" to holding register
10138 configures Meter 2’s Resettable Accumulator 3 to accumulate nothing
(takes it out of service).
The resettable accumulators are reset when one of the following situations occur.

Reset from AFC Manager
You may reset any of the resettable accumulators using the AFC Manager
(Meter Monitor):

Reset from Ladder Logic
The ladder logic may send a meter signals block to command one or more
resettable accumulators to be reset. This feature is especially important for
applications involving field installations that require shipping and/or receiving
product batches of predetermined size. Refer to the Ladder Logic section for your
module type for more information.