ProSoft Technology PTQ-AFC User Manual

Page 227

Advertising
background image

PTQ-AFC ♦ Modicon Quantum Platform

Reference

Liquid and Gas Flow Computer for Hydrocarbon Products

User Manual

ProSoft Technology, Inc.

Page 227 of 259

June 23, 2011

Description

Meter-Relative Address

Length

Resettable accumulator 2, totalizer

878 2

words

Resettable accumulator 2, residue

880 2

words

Resettable accumulator 3, totalizer

882 2

words

Resettable accumulator 3, residue

884 2

words

Resettable accumulator 4, totalizer

886 2

words

Resettable accumulator 4, residue

888 2

words

Accumulator, archive period, daily, totalizer

890 2

words

Accumulator, archive period, daily, residue

892 2

words

Accumulator, archive period, hourly, totalizer

894 2

words

Accumulator, archive period, hourly, residue

896 2

words

Process input, scaled float, temperature

1520 2

words

Process input, scaled float, pressure

1522 2

words

Process input, scaled float, dif prs / flow rate / freq

1524 2

words

Process input, scaled float, flowing density

1526 2

words

Process input, scaled float, water and sediment

1528 2

words

Process input, scaled integer, temperature

1540 1

word

Process input, scaled integer, pressure

1541 1

word

Process input, scaled integer, dif prs / flow rate / freq

1542 1

word

Process input, scaled integer, flowing density

1543 1

word

Process input, scaled integer, water and sediment

1544 1

word

Temperature, absolute

1570 2

words

Upstream pressure, absolute

1572 2

words

Densitometer frequency

1574 2

words

AGA 7 temperature base factor, Ftb

1594 2

words

AGA 7 pressure base factor, Fpb

1596 2

words

Meter alarms

1601 1

word

Orifice characterization error

1602 1

word

Analysis characterization error

1603 1

word

AGA 8 calculation error

1604 1

word

Density correction error

1605 1

word

Temperature correction error

1606 1

word

Vapor pressure error

1607 1

word

Pressure correction error

1608 1

word

Scan count, process input

1618 1

word

Scan count, calculation

1619 1

word

AGA 8, Molar mass of mixture

1620 2

words

AGA 8, Ideal gas relative density

1622 2

words

AGA 8, Compressibility at reference

1624 2

words

AGA 8, Molar density at reference

1626 2

words

AGA 8, Density at reference

1628 2

words

AGA 8, Relative density at reference

1630 2

words

AGA 8, Compressibility, flowing

1632 2

words

AGA 8, Molar density, flowing

1634 2

words

AGA 8, Density, flowing

1636 2

words

AGA 8, Supercompressibility, Fpv

1640 2

words

Previous timer tick count

1661 1

word

Scan period (seconds)

1662 2

words

Advertising
This manual is related to the following products: