Words 1 through 11 contain the meter process variables to be transferred from
the Quantum processor to the module. The contents of this block will depend on
the configured meter type (Differential or Linear), product group (Gas or Liquid)
and Primary Input (Standard) as follows:

Offset

Description Differential/Gas Differential/Liquid

Linear/Gas

Linear/Liquid

1

Process Variable 0

Reserved

Water% (SI)

Reserved

Water% (SI)

2

Process Variable 1

Temp (FP)

Temp (FP)

Temp (FP)

Temp (FP)

3

Process Variable 2

Temp (FP)

Temp (FP)

Temp (FP)

Temp (FP)

4

Process Variable 3

Press (FP)

Press (FP)

Press (FP)

Press (FP)

5

Process Variable 4

Press (FP)

Press (FP)

Press (FP)

Press (FP)

6

Process Variable 5

DiffPress (FP)

DiffPress (FP)

Pulses (DW)

Pulses (DW)

7

Process Variable 6

DiffPress (FP)

DiffPress (FP)

Pulses (DW)

Pulses (DW)

8

Process Variable 7

Reserved

Density (FP)

Reserved

Density (FP)

9

Process Variable 8

Reserved

Density (FP)

Reserved

Density (FP)

10

Process Variable 9

Reserved

Reserved

Pulse Freq (FP)

Pulse Freq (FP)

11

Process Variable 10

Reserved

Reserved

Pulse Freq (FP)

Pulse Freq (FP)

When Primary Input = Integration:

Offset

Description Differential/Gas

Differential/Liquid

Linear/Gas Linear/Liquid

1

Process Variable 0

Reserved

Water% (SI)

Reserved

Water% (SI)

2

Process Variable 1

Temp (FP)

Temp (FP)

Temp (FP)

Temp (FP)

3

Process Variable 2

Temp (FP)

Temp (FP)

Temp (FP)

Temp (FP)

4

Process Variable 3

Press (FP)

Press (FP)

Press (FP)

Press (FP)

5

Process Variable 4

Press (FP)

Press (FP)

Press (FP)

Press (FP)

6

Process Variable 5

Input Flow Rate (FP) Input Flow Rate (FP) Reserved

Reserved

7

Process Variable 6

Input Flow Rate (FP) Input Flow Rate (FP) Reserved

Reserved

8

Process Variable 7

Reserved

Density (FP)

Reserved

Density (FP)

9

Process Variable 8

Reserved

Density (FP)

Reserved

Density (FP)

10

Process Variable 9

Reserved

Reserved

Pulse Freq (FP)

Pulse Freq (FP)

11

Process Variable 10 Reserved

Reserved

Pulse Freq (FP)

Pulse Freq (FP)

FP = Floating Point (occupies 2 words)
SI = Scaled Integer
DW = Double Integer (occupies 2 words)