PTQ-AFC ♦ Modicon Quantum Platform

Quick Start

Liquid and Gas Flow Computer for Hydrocarbon Products

User Manual

ProSoft Technology, Inc.

Page 85 of 259

June 23, 2011

6.9 Modbus

Communication

A remote Modbus Master device can be connected to any one of the
communication ports for data polling. The module accepts the following Modbus
command functions according to the Modbus protocol specification:

Modbus Function Code

Description

3

Read Holding Registers

4

Read Input Registers

6

Preset (Write) Single Register

16

Preset (Write) Multiple Registers

Ports 2 and 3 support RS-232, RS-422, or RS-485 communications. The
Configuration/Debug port (Port 1) supports RS-232 only.
Refer to Cable Connections (page 133) for wiring instructions.
The Modbus Master command can be sent to either the Primary or Virtual
Modbus Slaves in the module. Each slave has individual Modbus addresses that
you can configure (Project / Site Configuration). The Primary Slave address is
configured as 244 by default.

6.9.1 Communication

Parameters

The module supports the following communication parameters for each
communication port:

Parameter

Values

Baud Rate

300, 600, 1200, 2400, 4800, 9600 or 19200

Data Bits

7 or 8

Stop Bits

1 or 2 Bits

Mode

RTU or ASCII

Parity

None, Even or Odd

Note: Do not configure a port for both RTU mode and 7 data bits as this combination is not
supported by the Modbus protocol.