Backplane Communication

PTQ-AFC ♦ Modicon Quantum Platform

User Manual

Liquid and Gas Flow Computer for Hydrocarbon Products

Page 180 of 259

ProSoft Technology, Inc.

June 23, 2011

Offset

Description Type

Comments

36

Select stream 1

Signal

Select stream 1 as active (v

 2.05 only)

37

Select stream 2

Signal

Select stream 2 as active (v

 2.05 only)

38

Select stream 3

Signal

Select stream 3 as active (v

 2.05 only)

39

Select stream 4

Signal

Select stream 4 as active (v

 2.05 only)

40

Reset Accumulator 1

Signal

41

Reset Accumulator 2

Signal

42

Reset Accumulator 3

Signal

43

Reset Accumulator 4

Signal

44

Write Daily Archive

Signal

45

Write Hourly Archive

Signal

46

Meter Signals - Reserved

Signal

47

Meter Signals - Reserved

Signal

48

Meter Signals - Reserved

Signal

49

Meter Signals - Reserved

Signal

50

Meter Signals - Reserved

Signal

51

Meter Signals - Reserved

Signal

52

Analysis is Present

Control

0 : analysis not present,
(v

 2.05) Analysis stream:

1 to 4 : stream number
-1 : active stream
(v

 2.04) <>0 : Analysis present

53

Meter Archive Record Fetch

Signal

(=0 signal not present)

54

Meter Archive Record Age

Output

(=0 current)

55

Meter Archive File Select

Output

(=0 daily, 1=hourly)