8 site datum point events – ProSoft Technology PTQ-AFC User Manual

Page 119

Advertising
background image

PTQ-AFC ♦ Modicon Quantum Platform

Quick Start

Liquid and Gas Flow Computer for Hydrocarbon Products

User Manual

ProSoft Technology, Inc.

Page 119 of 259

June 23, 2011

Tag

Rkv Description

1

-

Event Log Download
Value: Number of last-downloaded event.
Notes: Triggered by a purge of the Event Log, which marks older events
as available to be overwritten by new ones.

2

- Cold

Start

Value: Always 0.
Notes: This event is obsolete and is never written.

3

(1) Power-Up

Value: "Old" value is the last-saved wallclock from the previous session;
"new" value is always 0 (clock not yet set).
Notes: The last event written upon restart of the application and before
entering the meter scan. This event may be preceded by Checksum
Alarm and/or PLC Mode Change events.

4

-

PLC Mode Change
Value: PLC mode (0 on line, 1 off line).
Notes: Logs changes to PLC connectivity as reported by the backplane
procedures. Typically caused by switching the PLC between "run" and
"program" modes.

5

- Checksum

Alarm

Value: Checksum alarm word (datum type "Bsht").
Notes: Logs changes to the checksum alarm bitmaps.
Includes site/meter identification (bits 28-24).
Upon power-up:
Written automatically upon power up when a checksum failure is
detected. In this case the event is written even if the bitmap does not
change, such as when an affected bit is already set from a previous
failure that was never cleared.
Upon Modbus write to the bitmap:
Records changes to the bitmap only, typically when clearing bits, though
setting bits is also permitted.

6

(2) Wallclock

Change

Value: Wallclock (packed bitfields).
Notes: Triggered when the wallclock is set for the first time, or when it is
reset to a value that differs from its current value by five minutes or
more. These two cases can be distinguished by the "old value" in the
event entry: for the initial setting this value is zero ("clock not set").

7

* Stream

Select

Value: Stream number.
Notes: Triggered by a "select active stream" meter signal.
Includes meter identification (bits 28-24).

6.12.8 Site Datum Point events

Grup

Sbgp

Item

DTyp

Rkv

Data point

0

0

0

Bsht

(3)

Site options

1

Site parameter value

0

0

Flot

*

Barometric pressure

8

n

0

Usht

-

Arbitrary event-logged value "n" ("n" = 0 thru 9)

15

PLC image address (Quantum platform only)

0

0

Usht

*

Supervisory, get

1

0

Usht

*

Supervisory, put

2

0

Usht

*

Wallclock, get & put

3

0

Usht

*

Modbus gateway, get & put

Advertising
This manual is related to the following products: