Direct Control with Normal Security

Direct control with normal security is commonly used for operations that act on
local data (such as a LED test) or on data for which return information is not
supervised (for example switch on a heating). It uses the Operate and
TimeActivatedOperate services.

{This diagram and text has been taken directly from the IEC 61850 Standard
document.}

SBO (Select Before Operate) with Normal Security

SBO control with normal security first verifies that the Data Attribute is not
currently selected by a different Client; that it is operable; and that the operation
is not restricted. If this is verified, then the Operate request should proceed. It
uses these services:
S

ELECT

C

ANCEL

O

PERATE

T

IME

A

CTIVATED

O

PERATE

SBO with normal security Data Attributes are generally Controllable single point
(SPC) attribute types. These are things such as:
R

UN

D

IAGNOSTICS

T

RIGGER RECORDER

R

ESET RECORDER MEMORY

C

LEAR MEMORY