PLX8x-EIP-61850 ♦ Communication Gateway

Configuring the PLX8x-EIP-61850 Gateway

Server to

IEC 61850 Client

User Manual

ProSoft Technology, Inc.

Page 19 of 167

July 2, 2015

2.5

Importing a Project into the Configuration Manager

You can import an ProSoft 61850 Configuration Manager file that was created
and exported on a different PC. Do not try to open a project file created on
another PC, because it does not contain all the IED files that were used to create
it. Instead, use F

ILE

>

I

MPORT

C

ONFIGURATION

. This recreates all the

CID/SCD/ICD files that were part of the original configuration.

If you open a project not created on your PC instead of importing it, the Device
View shows a red slash through the IED files.

2.6

Configuring the Gateway EtherNet/IP Adapter

Configuring the gateway sets the permanent IP address for the gateway. It also
defines the NTP server that the gateway can poll for the current date and time.

Note: Since the PLX81-EIP-61850 has one physical Ethernet port, both EtherNet/IP and 61850

networks must be on the same subnet.


The PLX82-EIP-61850 has two physical Ethernet ports – one for each protocol. You must

configure these ports on different subnets.

1 Right-click the ProSoft Gateway bubble and choose P

ROPERTIES

. You can

also double-click the ProSoft Gateway bubble.