Hardware specifications plx8x-eip-61850, Leds – ProSoft Technology PLX81-EIP-61850 User Manual

Page 83

Advertising
background image

PLX8x-EIP-61850 ♦ Communication Gateway

Reference

Server to

IEC 61850 Client

User Manual

ProSoft Technology, Inc.

Page 83 of 167

July 2, 2015

5.2

Hardware Specifications PLX8x-EIP-61850

Specification

Description

Power Supply

24 VDC nominal
10 to 32 VDC power input allowed
Positive, Negative, GND Terminals
2.5 mm screwdriver blade

Current Load

200 mA maximum @ 24 VDC
150 mA maximum @ 32 VDC
450 mA maximum @ 10 VDC

Operating Temperature 32°F to 140°F (0°C to 60°C)
Storage Temperature

-40°F to 185°F (-40°C to 85°C)

Relative Humidity

5% to 95% RH, with no condensation

Dimensions

Standard: Height x Width x Depth
4.72 inches x 1.90 inches x 4.18 inches

Ethernet Port (E1)

10/100 Base-T half duplex RJ45 Connector
Link and Activity LED indicators
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as
specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP]
frames-per-second and less than or equal to 5 minutes duration

LED Indicators

ERR, CFG, FLT, PWR

Shock and Vibration

Shock and Vibration tested to EN 60068 Standard

Shipped with Each Unit One - Ethernet straight-through cable

One - J180 screw terminal plug
One - ProSoft Solutions DVD
One - HRD250 screwdriver
One - 1GB Industrial SD Card

5.3

LEDs

LED

State

Description

Pwr

Off

Power is not connected to the power terminals or source is
insufficient to properly power the gateway (800mA at 24 VDC
minimum required)

Pwr

Green Solid

Power is connected to the power terminals. Verify that the other
LEDs for operational and functional status come on briefly after
power-up (check for burned-out LEDs).

Flt

Off

Normal operation

Flt

Red Solid

A critical error has occurred. Program executable has failed or has
been user-terminated and is no longer running. Press Reset p/b or
cycle power to clear error.

Cfg

Off

Normal operation

Cfg

Amber Solid

The unit is in configuration mode. The configuration file is currently
being downloaded or, after power-up, is being read, the unit is
implementing the configuration values, and initializing the hardware.
This occurs during power cycle, or after pressing the reset button. It
also occurs after a cold/warm boot command is received.

Err

Off

Normal operation

Err

Flashing

An error condition has been detected and is occurring on one of the
application ports. Check configuration and troubleshoot for
communication errors.

Err

Solid Amber

This error flag is cleared at the start of each command attempt

Advertising
This manual is related to the following products: