PLX8x-EIP-61850 ♦ Communication Gateway

Reference

Server to

IEC 61850 Client

User Manual

ProSoft Technology, Inc.

Page 81 of 167

July 2, 2015

Class 3 Explicit Server
The database tags mapped to the Class 3 tab can be accessed by using MSG
instructions in the PLC. Mapping the tags into the Class 3 tab makes the tags
accessible by Class-Instance-Attribute and by tag name. The connection:
 Accepts incoming messages from two additional EtherNet/IP clients.
 Supports up to 500 individually mapped tags on Class 3 connections

EtherNet/IP server
functions supported

Class 1 Implicit I/O connection

Class 3 Explicit messaging

Class 1 server
support

Up to 10 Generic EtherNet/IP CIP Bridge connections (PLX81)

Up to 20 Generic EtherNet/IP CIP Bridge connections (PLX82)

500 Bytes Input data/ 496 Bytes Output data per connection

RPI time selectable on each connection

Class 3 server
support

Two Class 3 servers supported

Up to 500 Data Attributes can be mapped to Class 3 connections

Status data for EtherNet/IP network, IEC 61850 network, and
module are mapped to a Class 3 attribute

.