ProSoft Technology PLX81-EIP-61850 User Manual

Page 63

Advertising
background image

PLX8x-EIP-61850 ♦ Communication Gateway

Diagnostics and Troubleshooting

Server to

IEC 61850 Client

User Manual

ProSoft Technology, Inc.

Page 63 of 167

July 2, 2015

Configuration Settings

Setting

Description

TimeOut

The value in seconds for the command to timeout from a
request

GOOSE Support

TRUE or FALSE value, indicating if GOOSE messaging is
supported and configured on the gateway

Sampled Values Support

TRUE or FALSE value, indicating is Sampled Values is
supported and configured on the gateway

Number of Remote Addresses

The count of remote addresses present in the current
operating configuration of the gateway, in the IEC-61850
driver

Reports Configured

TRUE or FALSE value in driver indicating if reports are
currently configured in the IEC-61850 driver

Number of Commands

The total count of Read and Write commands present in the
current operating configuration of the IEC-61850 driver

Number of GOOSE Subscriptions

The total count of GOOSE subscriptions present in the
current operating configuration of the IEC-61850 driver

Number of Reports Configured

The total count of reports (Buffered and Unbuffered) present
in the current operating configuration of the IEC-61850
driver

Driver Status

Status

Description

Remote Node Status

This displays a bitmap of 1s or 0s, to indicate the
communication status of each IED where 1=communication is
good, and 0=no communication.

Command Read Requests

The count of total IEC61850 (MMS type) read command
requests sent to nodes defined in the configuration file

Command Write Requests

The count of total IEC61850 (MMS type) write command
requests sent to nodes defined in the configuration file

Command Read Errors

The count of total IEC61850 (MMS type) read errors received
from requests sent to nodes defined in the configuration file

Command Write Errors

The count of total IEC61850 (MMS type) write errors received
from requests sent to nodes defined in the configuration file

GOOSE messages Processed

The total count of GOOSE messages received per all
subscriptions defined in the current operating configuration of
the IEC61850 driver

Report Messages Processed

The total count of reports received per all reports that are
enabled, and present in the current operating configuration of
the IEC61850 driver

Identification Response Errors

The total count of Identification response errors per the
nodes/devices defined in the current operating configuration
of the IEC61850 driver

Create DataType Errors

The total count of errors received when making a request for
datatypes defined for the configured commands in the current
operating configuration of the IEC61850 driver