5.4.2 Tag Database

The Tag Database is a key part of the internal workings of the gateway. Upon
restart, the Tag Database reads the configuration file, and process the tags. Data
is stored in the gateway’s memory, and referenced through tag names. The
number of tags is limited to the memory capability of the hardware and the
process memory required by gateway.

The data of varying data types are stored in the gateway. This impacts that
maximum number of tags the gateway can hold.

Some data types are considered Native data types to the gateway, and some are
considered Complex. Complex data types are for the creation of the user-defined
data types, which are necessary for many IEC 61850 data types.

Native data types

Native data types are the data types used internal to the gateway. When the data
is transferred from IEC 61850 to EtherNet/IP, it is first stored in the tag database,
using the following data types:

Name

Definition

Bits

BOOL

Boolean

1

BYTE

Byte

8

UBYTE

Unsigned Byte

8

INT

Integer

16

UINT

Unsigned Integer

16

DINT

Double Integer

32

UDINT

Unsigned Double Integer

32

REAL

IEEE 754 Single Precision Floating-Point

32

DREAL

IEEE 754 Double Precision Floating-Point

64

STRING

ASCII Character Array

32 + 8* Length

DATETIME

UTC microsecond precision date and time

64