PLX8x-EIP-61850 ♦ Communication Gateway

User Manual

Server to

IEC 61850 Client

Page 122 of 167

ProSoft Technology, Inc.

July 2, 2015

T

YPE

: This is the IEC-61850 data type of the tag.

IEC 61850 Data Type

Number of Bytes

BOOLEAN

1

INT8

1

INT16

2

INT24

4

INT32

4

INT128

Not Supported

INT8U

1

INT16U

2

INT24U

4

INT32U

4

FLOAT32

4

FLOAT64

Not Supported

Enum

2

Dbpos

2

Tcmd

1

Quality

2

Timestamp

8

VisString32

102

VisString64

102

VisString255

102

Octet64

64

EntryTime

4

Unicode255

102

BitString

1

Check

1

When you choose E

XPORT

AOI

F

ILES

, ProSoft ProSoft 61850 Configuration

Manager prompts you for a location of the AOI for each IED defined in the
project. The Add-On Instruction file (.L5X) contains Tag Names, Data Types and
the logic rungs to be used in an RSLogix 5000 project.

5.7.2 Example: Energy Application:

 The IEC 61850 protocol specification was written with electrical substations in

mind.

 The PLC wants all data you have defined as relevant, including time stamp

and quality bits from all IEDs. It sends this data to a dispatching system. In
this case, the PLC is like a data concentrator from the substation to the
dispatching center.

 You wantss Open and Close control with tight time constraints. The controls

need to be as fast as possible.

One typical example for this kind of application might be 20 IEDs, where the
gateway needs to send all the relevant data from all 20 IEDs to the PLC.
Typically, this would be approximately 250 data points per IED.