ProSoft Technology PLX81-EIP-61850 User Manual

Page 59

Advertising
background image

PLX8x-EIP-61850 ♦ Communication Gateway

Diagnostics and Troubleshooting

Server to

IEC 61850 Client

User Manual

ProSoft Technology, Inc.

Page 59 of 167

July 2, 2015

The PLC can read the value value by polling for the tag names
“EIPS_Connection_Status”, “IED_Node_Status”, or “Module_Driver_Status”
using a Class 3 MSG instruction as shown below (in RSLogix 5000).


The “Destination Element” of the RSLogix 5000 MSG instruction should be of
data type SINT.

Alternatively, you can configure a MSG instruction to poll for Class 0x300
Instance 0x01 and Attribute (as listed in the Class 3 MSGs tab). Below is a
sample MSG configuration using Class, Instance, Attribute messaging.

Again, the D

ESTINATION

E

LEMENT

should be of data type SINT, and must contain

enough members based on the size of the data to obtain from the gateway.