PLX8x-EIP-61850 ♦ Communication Gateway

User Manual

Server to

IEC 61850 Client

Page 98 of 167

ProSoft Technology, Inc.

July 2, 2015

{This table has been taken directly from the IEC 61850 Standard document.}

setMag
 You must set this for APC (Controllable Analogue Set Point Information)

CDC.

operTm
 The PLC user sends a command with operate time to the gateway, and the

gateway uses time activated control, e.g. it sends the time of operation to the
IED. The IED needs to support the time activated control.

origin.orCat
 The orCat could have these values. The value depends upon the role of the

PLC. E.g. if the PLC is a station control, then this value never changes.

not-supported

orCat is not supported

bay-control

Control operation issued from an operator using a Client located at bay level

station-control

Control operation issued from an operator using a Client located at station
level

remote-control

Control operation from a remote operater outside the substation (for example
network control center)

automatic-bay

Control operation issued from an automatic function at bay level

automatic-station Control operation issued from an automatic function at station level

automatic-remote Control operation issued from a automatic function outside of the substation

maintenance

Control operation issued from a maintenance/service tool

process

Status change occurred without control action (for example external trip of a
circuit breaker or failure inside the breaker)

origin.orIdent
 This is the address of the originator. The value you want depends upon the

role of the PLC.

ctlNum
 This is of no consequence to the IED and only appears in reports. This is an

optional parameter. The ctlNum may be of interest to you when the Client
uses the same control number for a complete control sequence: select,
operate, …