Reference

PLX8x-EIP-61850 ♦ Communication Gateway

User Manual

Server to

IEC 61850 Client

Page 90 of 167

ProSoft Technology, Inc.

July 2, 2015

The assignment of the DATA-SET to a BRCB, URCB, or GOOSE Control Block
is set on the IED. These DATA-SET definitions are currently outside the scope of
the gateway. See the BRCB, URCB, and GOOSE sections of this document to
understand how DATA-SETs are used by the gateway, and for examples.

{This diagram has been taken directly from the IEC 61850 Standards document.}

5.5.3 Report Control Block

This section describes the gateway’s implementation of IEC 61850-7-2 Clause
14: REPORT-CONTROL-BLOCK.

Log and logging is not supported at this time.

The Report Control Block (RCB) is made available to you through ProSoft 61850
Configuration Manager. The parsing of the CID/SCD file discovers the
ReportControl element, which is unique within the Logical Node (LN). ProSoft
61850 Configuration Manager presents the ReportControl items to you, for you to
map to the other protocol in the gateway, if required or desired.

Supported Report Control Block Features
 RptEnabled
 TrgOps
When the gateway is configured to use an IED’s report, after the gateway
establishes a connection with the IED, it turns on RptEnabled. The gateway then
receives the reports its configured to receive.

TrgOps tells the gateway which internal event produces the inclusion of a DATA-
SET member onto a report. TrgOps options are:
 Data change (dchg)
 Quality change (qchg)
 Data update (dupd)
 General Interrogation
The reason for inclusion of a piece of data in the report is because the IED is
dependent upon the TrgOps (Trigger Options) in the CID/SCD file.