Configuring the PLX8x-EIP-61850 Gateway

PLX8x-EIP-61850 ♦ Communication Gateway

User Manual

Server to

IEC 61850 Client

Page 26 of 167

ProSoft Technology, Inc.

July 2, 2015

2.10.1 Mapping MMS Messages

MMS messages can be read-only (read the value from the IED) or write (write
the value to the IED).

1 In the Network View pane in the EIP-61850 Configuration Manager, right-click

the IED bubble that you want to map, and choose C

ONFIGURE

.

This displays the IEC 61850 Mapping Tool window.

2 In the treeview on the left, expand (click the + sign) the root folder. This

shows the Logical Devices (notice the little LD in the icon) in the IED.

3 Expand (click the + sign) on one of the Logical Devices in the IED to see the

Logical Nodes (notice the little LN in the icon) within it. Some IED
manufacturers provide descriptive information in their CID files. ProSoft
ProSoft 61850 Configuration Manager displays that information after the
Logical Node name.

4 Continue to expand the Logical Node to display the Data Object (DO) and

finally the individual Data Attributes.