Adding the Gateway to RSLogix 5000

PLX8x-EIP-61850 ♦ Communication Gateway

User Manual

Server to

IEC 61850 Client

Page 50 of 167

ProSoft Technology, Inc.

July 2, 2015

3.4

Download the project to the processor to verify the connection

1 Save, and then download the project to the processor.
2 A yellow triangle in RSLogix 5000 means an error on connection. Check that

the Output size and Input size for the Class 1 connection in the gateway
configuration matches and the Comm Format is SINT. Try increasing RPI
time of module if the error persists.

3 If errors persist, re-download the configuration to make sure that the module

configuration matches the configured RSLogix 5000 program.

4 For additional troubleshooting, use the ProSoft EIP-61850 Configuration

Manager. Right-click the ProSoft Gateway bubble, and choose D

IAGNOSTIC

.

Class 1 displays the connection RPI time of processor and the IP address of
the ENBT. The open connection count starts at 1 and increments if the
connection to the processor is interrupted or there is a connection timeout.
State, open connection, and connection timeout are controlled by the code.

You can change the RPI and Ethernet IP in the ladder configuration in
RSLogix 5000 (right-click connection0 and choose P

ROPERTIES

).