2 troubleshooting – GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 114

Advertising
background image

Multipoint functions

114

7

7.2.2 Troubleshooting

Multi-Source Ground Fault Setting Change Rejected events are observed in the Sequence of
Events log

Verify that the pickup setting is within the valid range. Valid range is from “Zone Minimum
Pickup” to 1200 Amps. (See

Setting Multi-Source Ground-Fault pickup/delay on page 111

.)

Backup relay is not working

Verify that the backup function is enabled for the concerned zone in the concerned topology.

Frequent suspended/resumed events are seen

Verify that both CPUs are operating with the hardware clock. This can be done from the
System Health screen. The Synchronization hardware OK indicator lights should be green for
both CPUs.

7.2.3 Events generated by Multi-Source Ground-Fault Relay

To view a table of events generated by the Multi-Source Ground-Fault Relay, see

Alarms and

events on page 213

.

7.2.4 Alarms generated by Multi-Source Ground-Fault Relay

To view a table of alarms generated by the Multi-Source Ground-Fault Relay, see

Alarms and

events on page 213

.

Advertising