2 troubleshooting – GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 147

Advertising
background image

High Current Trigger relay

147

9

Alarm Group Box

Pickup (x LT Pickup) - 0.1 to 9 in steps of 0.1

Delay (Half cycles) - 1 to 120 in steps of 1 (Half cycle refers to the AC Power signal and thus
for a 60Hz system, 1 half cycle = 8.333ms)

Waveform Group Box

Maximum number of waveform triggers - 0 to 30, 0 disables waveform capture

Reset Count - Resets the number of waveforms triggered (Does not affect the stored
waveforms)

9.3.2 Troubleshooting

Condition: The event logs shows where the High Current Trigger Relay triggered but there
are no waveforms

Solution: The waveforms will not be recorded if:

• “The Waveform Capture Enable” checkbox is unchecked
• The Waveform buffers are full and waveform protection is enabled
• The “Maximum Number of Waveforms” have been met