2 user settings for multi-source ground-fault – GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 134

Advertising
background image

Reduced Energy Let-Thru Mode

134

8

8.3.2 User settings for Multi-Source Ground-Fault

The minimum settings for Multi-Source Ground-Fault zones for both Alarm-Only and Trip
Relays for Topology 0 are:
Pickup Setting

= 30 Amps

Time Delay

= BAND 1

Curve I

2

T

= DISABLED

Backup Function (For Trip Relay only)

= ENABLED

Backup Time Delta (For Trip Relay only)

= Trip Immediately

For all MSGF summation zones for both Alarm-Only & Trip Relays for Topology 0
Pickup Setting

= 30Amps

Time Delay

= BAND 1

Curve I

2

T

= DISABLED

Figure 8-6 Reduced Energy Let-Thru Mode settings for Multi-Source Ground-Fault Relay

NOTE: Although the Pickup is set to 30 Amps, Entellisys automatically enforces a “Zone
Minimum Pickup Setting” for Multi-Source Ground-Fault. The “Zone Minimum Pickup Setting” is
20% of the largest CT rating in the corresponding zone.